General Description
The Marvair
®
Classic wall mounted heat pumps are the ideal HVAC system
for a wide variety of applications. The exterior mounting means that no
valuable interior space is required. The Classic heat pumps are packaged
units the refrigerant piping and internal wiring are factory assembled
and thoroughly tested. All components are readily accessible for easy
service and maintenance. The energy efficient operation keeps operating
costs to a minimum and makes the Marvair heat pumps ideal problem
solvers for a wide variety of applications, including offices, classrooms and
telecommunication shelters.
Three Series to meet any Budget or Efficiency Requirement - Three
series of Classic heat pumps are available. The Classic HVPA models are
our most efficient models and feature EERs (Energy Efficiency Ratio) of up
to 11.50. No wall mount heat pump is more efficient. The HVPSA models
feature a 2-stage compressor that matches the cooling capacity to the
heat load. Our AVPA models have EERs of up to 9.75. The AVPA & HVPA
(single stage compressor units) are built in nominal cooling capacities of
2, 2½, 3, 3½, 4 and 5 tons. The HVPSA (2-stage compressor) units are
available in nominal cooling capacities of 3, 3½, 4 and 5 tons.
Outside Air for Ventilation or Free Cooling
- A full range of accessories and options allows the Classic
heat pumps to be optimized for each application. For classrooms, a complete range of ventilation
options are available to meet the fresh air requirements of the ASHRAE 62 standard, “Ventilation
for Acceptable Indoor Air Quality”, including the exclusive Marvair GreenWheel
®
Energy Recovery
Ventilator. Where cooling is required during cool or cold weather, e.g., telecommunications shelters, a
factory installed economizer should be used. To insure proper operation and optimum performance, all
outside air ventilation packages are non-removable, factory installed and factory calibrated.
2-Stage Compressor -The HVPSA models feature a two stage compressor with a first stage capacity
of 65% of the total capacity. The two stage compressor offers better comfort by maintaining more
precise temperature and relative humidity levels with improved overall energy efficiency. During mild
days, the first stage can satisfy the load, minimizing temperature fluctuations providing steady, even
comfort. With Integrated Part Load Performance Values (IPLV) of up to 15.0, the Classic heat pump
with the two stage, high efficiency compressor can provide significant energy savings compared to
older, less efficient systems. The cooling mode has two stage operation; heating is single stage.
Quiet in the Classroom - In addition to high efficiency, the HVPA and HVPSA models minimize sound
levels in the classroom. A high efficiency axial fan moves air silently through the outdoor
coils. A low vibration, scroll compressor insures quiet operation as well as energy efficiency.
The indoor air mover utilizes a revolutionary electronically commutated motor (ECM). This
motor consumes a minimum of power with whisper quiet operation. The ECM automatically
adjusts its speed to maintain the proper air flow at various external static pressures.
Safety Listed and Energy Certified - All Classic heat pumps are built to UL standard 1995, 4th
edition and CAN/CSA C22.2, No. 236-11, 2nd edition. For energy efficiency and performance, the
units are tested and rated in accordance to the ANSI/AHRI (Air-Conditioning Heating and Refrigeration
Institute) Standard 390 (Single Package Vertical Units). All units meet or exceed the efficiency
requirements of ANSI/ASHRAE/IESNA 90.1.2007. The Classic heat pumps are commercial units and
are not intended for use in residential applications.
Dehumidification - The introduction of outside air can cause humidity levels to rise to unacceptable
levels. To reduce humidity, the Classic heat pumps can be ordered with a Hot Gas Reheat (HGR) coil.
The HGR coil allows the heat pump to dehumidify without adversely lowering the temperature in the
classroom and uses less energy than electric reheat. When used in conjunction with the GreenWheel
®
ERV, humidity levels can be controlled at a minimum of expense. See page 4 for a detailed description
of the operation of the Hot Gas Reheat Coil.
Classic Heat Pumps
Vertical Packaged Heat Pumps
Single stage cooling models AVPA24-30-36-42-48-60 and
HVPA24-30-36-42-49-60 and
2-stage cooling models HVPSA36-42-49-60
Classic AVPA, HVPA & HVPSA PDS 8/2013 rev.5
Page view 0
1 2 3 4 5 6 ... 31 32

Summary of Contents

Page 1 - Classic Heat Pumps

General DescriptionThe Marvair® Classic wall mounted heat pumps are the ideal HVAC system for a wide variety of applications. The exterior mounting

Page 2 - Classic™ Heat Pump Features

Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5 10 Summary Electrical Ratings (Wire and HACR Circuit Bre

Page 3 - Energy Recovery Ventilator

11 Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5Summary Electrical Ratings (Wire and HACR Circuit Bre

Page 4 - Heat Pump PC Board

Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5 12 Unit Load Amps (Heating) -AVPA Heat Pumps with Ventil

Page 5 - Classic Heat Pump Options

13 Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5Certified Efficiency and Capacity Ratings at ANSI/ARI

Page 6 - Accessories

Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5 14 Electrical Characteristics -Compressor, Fan, Ventilat

Page 7

15 Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5Summary Electrical Ratings (Wire and HACR Circuit Bre

Page 8

Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5 16 Summary Electrical Ratings (Wire and HACR Circuit Bre

Page 9 - AVPA Heat Pumps

17 Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5Unit Load Amps (Heating) -HVPA Heat Pumps with Single

Page 10

Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5 18 Certified Efficiency and Capacity Ratings at ANSI/ARI

Page 11

19 Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5Electrical Characteristics - HVPSA Heat Pumps - 2-Sta

Page 12

Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5 2 Outside Air for VentilationASHRAE standard 62 requires

Page 13

Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5 20 Summary Electrical Ratings (Wire and HACR Circuit Bre

Page 14

21 Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5Summary Electrical Ratings (Wire and HACR Circuit Bre

Page 15

Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5 22 Summary Electrical Ratings (Wire and HACR Circuit Bre

Page 16

23 Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5Unit Load Amps (Heating) -HVPSA Heat Pumps w/2-Stage

Page 17 - Unit Load Amps (Heating)

Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5 24 Unit Load Amps (Heating) - HVPSA Heat Pump with 2-sta

Page 18 - HVPSA24HP HVPSA30HP

25 Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5Dimensional Data for AVPA24 (inches and mm)Shipping W

Page 19

Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5 26 Dimensional Data for AVPA30/36 and HVPA24 Shipping We

Page 20

27 Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5Dimensional Data for AVPA42/48/60, HVPA30/36/42 andHV

Page 21

Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5 28 Dimensional Data for HVPA49/60 andHVPSA49/60 (inches

Page 22

29 Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5Dimensional Data for AVPA24/30/36 and HVPA24 with the

Page 23

3 Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5Classic Heat Pump Ventilation OptionGreenWheel® ERV ex

Page 24 - GreenCube

Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5 30 Dimensional Data for AVPA42/48/60, HVPA30/36/42,&

Page 25 - Filter Size

31 Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5Notes

Page 26

Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5 32 P.O. Box 400 • Cordele, GA 31010156 Seedling Drive

Page 27 - HVPSA36/42 (inches and mm)

Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5 4 EconomizerThe economizer reduces the cost of air

Page 28 - HVPSA49/60 (inches and mm)

5 Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5By moving a pin on the board, the user can have electr

Page 29

Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5 6 Classic Heat Pump Model IdentificationAVP = Air Source

Page 30

7 Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5With built-in temperature and humidity sensors, motion

Page 31

Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5 8 Certified Efficiency and Capacity Ratings at ANSI/ARI

Page 32 - • Internet: www.marvair.com

9 Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2013 rev.5Air Flow (Cubic Feet per Minute)Model NumberExternal S